Heating and cooling degree days in Washington, DC

Last 12 months, through October 2026: 3,899 heating degree days (HDD) and 1,910 cooling degree days (CDD) at base 65 °F. That is 1 % more heating than the 1991-2020 average of 3,868 HDD, and 1,910 CDD against 1,667.

Monthly degree days in Washington, DC, base 65 °F

The last 24 complete months, through October 2026, from NOAA GHCN-Daily station Washington Reagan Natl Ap (USW00013743), 6.7 km from the city centre. Beside each month, the mean of the same month over the ten years before (grey).

0491982Nov 2025: 443 HDDNov 2025: 0 CDDTen-year mean: 442 HDDTen-year mean: 6 CDDNovDec 2025: 859 HDDDec 2025: 0 CDDTen-year mean: 711 HDDTen-year mean: 0 CDDDecJan 2026: 982 HDDJan 2026: 0 CDDTen-year mean: 821 HDDTen-year mean: 0 CDDJanFeb 2026: 807 HDDFeb 2026: 0 CDDTen-year mean: 618 HDDTen-year mean: 0 CDDFebMar 2026: 397 HDDMar 2026: 14 CDDTen-year mean: 466 HDDTen-year mean: 5 CDDMarApr 2026: 175 HDDApr 2026: 86 CDDTen-year mean: 215 HDDTen-year mean: 42 CDDAprMay 2026: 92 HDDMay 2026: 118 CDDTen-year mean: 65 HDDTen-year mean: 132 CDDMayJun 2026: 0 HDDJun 2026: 382 CDDTen-year mean: 1 HDDTen-year mean: 350 CDDJunJul 2026: 0 HDDJul 2026: 518 CDDTen-year mean: 0 HDDTen-year mean: 529 CDDJulAug 2026: 0 HDDAug 2026: 467 CDDTen-year mean: 0 HDDTen-year mean: 452 CDDAugSep 2026: 16 HDDSep 2026: 271 CDDTen-year mean: 7 HDDTen-year mean: 261 CDDSepOct 2026: 128 HDDOct 2026: 54 CDDTen-year mean: 131 HDDTen-year mean: 61 CDDOct
MonthHDDCDDHDD 10-yr meanCDD 10-yr mean
Oct 20261285413161
Sep 2026162717261
Aug 202604670452
Jul 202605180529
Jun 202603821350
May 20269211865132
Apr 20261758621542
Mar 2026397144665
Feb 202680706180
Jan 202698208210
Dec 202585907110
Nov 202544304426
Oct 20251692313161
Sep 202502167261
Aug 202503330452
Jul 202505400529
Jun 202583661350
May 20254310565132
Apr 20251656421542
Mar 2025358254665
Feb 202567006180
Jan 202595108210
Dec 202471607110
Nov 2024324284426

Long-term average, 1991-2020

Mean degree days per calendar month at base 65 °F over the 30 years of the current US climate normals, same station: 3,868 HDD and 1,667 CDD a year.

MonthHDDCDD
Jan8660
Feb7170
Mar5563
Apr24828
May72128
Jun4328
Jul0482
Aug0431
Sep15225
Oct18641
Nov4662
Dec7390
Year3,8681,667

For comparison, NOAA's published 1991-2020 normal for the same station is 3,769 HDD and 1,738 CDD a year. NOAA fills missing days and adjusts records for changes at the station before averaging; the numbers here use the record as it stands, so the two can differ by a few per cent.

Other base temperatures, periods and sites

Degree days at 65 °F are the US convention; many buildings balance lower, at 55 or 60 °F, and Europe often uses 15.5 or 18 °C. The degree-day tool takes any point and any base in °F or °C. The last 24 months for any point and any base temperature are free on screen, no account needed. A CSV of any period since 1950, daily or monthly, at any base, costs 1 credit. A site whose new month of degree days is emailed to you on the 2nd costs 1 credit a month, and stops when you remove it. The same exports work through the API with your key.

Method: for each day the mean temperature is the average of the day's maximum and minimum; heating degree days are the degrees the mean falls below 65 °F, cooling degree days the degrees it rises above, summed over the month. This is the mean-temperature method of NOAA's climate normals. It uses daily records, not hourly ones, so it is not the hourly integration method some providers use, and a day that crosses 65 °F can count a little differently. A month with a few days missing is estimated from its other days; a month with more than 20 % of its days missing has no value. The station is the NOAA station nearest the city centre with a complete record; your building may be better served by another station or by the value at its own point, which the lookup gives.

Nearby cities

Baltimore · Philadelphia · New York · Columbus · Charlotte · Boston · all 30 cities

For an EnergyPlus model of a building in Washington, the same site gets hourly weather files: a typical year, actual years for calibration and design conditions.

Frequently asked questions

How many heating degree days does Washington, DC have a year?

About 3,868 at base 65 °F on the 1991-2020 average, from Washington Reagan Natl Ap.

How many cooling degree days does Washington, DC have a year?

About 1,667 at base 65 °F on the 1991-2020 average.

How are these degree days calculated?

From each day's maximum and minimum temperature: the mean of the two against the base, summed over the month. Hourly data are not used.

Can I download degree days for my own building?

Yes. The last 24 months for any point and base are free on screen; a CSV of any period costs 1 credit.

Degree days for your own site

Free to try, no credit card.

Open the degree-day tool →